Inverter Series0 pages
200 VA - 12 kVA
Inverter Series
UPS/INVERTERS
www.powersolve.co.uk
•
Sinusoidal Output from 12-480 V
•
Compact Switched Mode Design
•
DC Inputs 10-400 V
•
Wall or Rack Mounting
•
Industrial Grade
•
Customised Design Available
Specification
Input
General
Input Voltage
• See Table
No load Input Power
• 20 W typical
Earth Leakage Current • <3.5 mA at 230 VAC
Efficiency
Dimensions/Weight
• 85-95% I models,
75-90% CI, IT & IV models
• 3500 VDC Input to Output,
3500 VDC Input to Ground,
3500 VDC Output to Ground
• Approx 33 kHz converter & 20 kHz
Inverter section
• 120,000 hours I & IT models,
70,000 hours CI models,
50,000 hours IV models
• Contact Sales
Options
• Contact Sales
Isolation
Output
Output Voltage
Output Voltage
Adjustment
Minimum Load
Wave Form
Frequency
Distortion
Rise Time
Power Factor
Crest Factor
Line Regulation
Load Regulation
Overload
Protection
Short Circuit
Current
Surge Power
Temperature
Coefficient
• See Table
• 110 V version 110 V to 125 V
230 V version 210 V to 245 V
• No minimum load required
• Sinusoidal standard, optional wave
shape programmable
by external signal
• Crystal stabilized 50 Hz, 60 Hz,
400 Hz or 45 to 400 Hz adjustable
• 3% typical (5% at 400 Hz)
• 100 ms typical
• Cos Ø≥0.7 inductive/capacitive
• 3
• 0.1% for CI models,
2.0 % for I, IT & IV models
(±10% change Vin)
• 50/60 Hz 1% typical 3% max,
400 Hz 3% typical 5% max
(10-90% load change)
• Current limited to approx 105%
I Nom (Steady State)
• Electronically limited to 3 x I Nom
Switching Frequency
MTBF
Environmental
Operating Temperature • -20 °C to +75 °C, derate linearly at
2.5%/°C from +55 °C
Optional -40 °C to +75 °C
Storage Temperature
• -40 °C to +85 °C
Cooling
• Natural convection
(IT5600 to IT5800 forced cooled)
Operating Humidity
• 5-95% RH non-condensing
Operating Altitude
• 1000 m
EMC & Safety
Emissions
EFT/Burst
Surge
Safety Approvals
• EN55022 Level A conducted,
optional Class B
• EN61000-4-4 Level 3
• EN61000-4-5 Level 3
• EN60950
• 2 x P Nom for 1 sec
• 0.05%/°C typical
Powe
rsolve Electronics Ltd. 8A, Arnhem Road, Newbury, RG14 5RU. England
Tel:01635 521858 Fax: 01635 523771 Email: sales@powersolve.co.uk