Fasmetal? 10 HVAC Repair0 pages
Technical Data Sheet
4/17/2012
Fasmetal™ 10 HVAC Repair
Description:
An aluminum-filled, 1:1 mix epoxy packaged in 6 1/2 oz. tube kit for repairs to copper coils in HVAC equipment.
Intended Use:
Seal leaks in pipes and tanks; repair copper coils in compressors; repair holes in aluminum and other metals
Product
features:
Fills voids or pores in castings
Bonds, patches, and seals metals
Good stability in Freon Environment
Bonds to aluminum, concrete, and many other metals
Aids in quickly returning equipment back to service
Hardens to a rigid material that can be ground, drilled, or tapped
Limitations:
Not recommended for long term exposure to concentrated acids and organic solvents
Typical
Physical
Properties:
Technical data should be considered representative or typical only and should not be used for specification purposes.
Surface
Preparation:
Cured 7 days @ 75° F
Adhesive Tensile Shear
Coefficient of Thermal Expansion
Color
Compresive Strength
Coverage/lb
Cured Hardness
Cured Shrinkage
Dielectric Constant
Dielectric Strength
Flexural Strength
Functional Cure
Mix Ratio by Volume
Mix Ratio by Weight
Mixed Viscosity
Modulus of Elasticity
Pot Life @ 75F
Recoat Time
Solids by Volume
Specific Gravity
Specific Volume
Temperature Resistance
Thermal Conductivity
2,500 psi
29 [(in.) x (in). x ° x 10(-6)
F)]
Aluminum
8,420 psi
30 sq.in./6.5 oz. @ 1/4"
85D
0.0008 in./in.
21.4
100 volts/mil
6,260 psi
16 hrs.
1:1
0.9:1
40,000 cps
7.8 psi x 10(5)
60 min.
10-12 hrs.
100
1.72 gm/cc
16.1 in.(3)/lb.
Wet: 110° Dry: 250°
F;
F
1.73[cal/(secxcmx°
C)]x10(-3)
TESTS CONDUCTED
Compressive Strength ASTM D 695
Cured Hardness Shore D ASTM D 2240
Dielectric Constant ASTM D 150
Modulus of Elasticity ASTM D 638
Cure Shrinkage ASTM D 2566
Adhesive Tensile Shear ASTM D 1002
Dielectric Strength, volts/mil ASTM D 149
Coef. of Thermal Expansion ASTM D 696
Flexural Strength ASTM D 790
Thermal Conductivity ASTM C 177
1. Thoroughly clean the surface with Devcon® Cleaner Blend 300 to remove all oil, grease and dirt.
2. Grit blast surface area with 8-40 mesh grit, or grind with a coarse wheel or abrasive disc pad, to create increased
surface area for better adhesion (Caution: An abrasive disc pad can only be used provided white metal is revealed).
Desired profile is 3-5mil, including defined edges (do not "feather-edge” epoxy).
Note: For metals exposed to sea water or other salt solution, grit-blast and high-pressure-water-blast the area, then leave
overnight to allow any salts in the metal to “sweat” to the surface. Repeat blasting to “sweat out” all soluble salts. Perform
chloride contamination test to determine soluble salt content (should be no more than 40ppm).
3. Clean surface again with Devcon® Cleaner Blend 300 to remove all traces of oil, grease, dust or other foreign
substances from the grit blasting.
4. Repair surface as soon as possible to eliminate any changes or surface contaminants.
WORKING CONDITIONS: Ideal application temperature is 55° to 90° In cold working conditions, directly heat repair
F
F.
area to100-110° prior to applying epoxy and maintain at this temperature during product cure to dry off any moisture,
F
ITW Polymers Adhesives North America , 30 Endicott Street, Danvers, MA 01923