EB5000 pages
EB500
1 Shot Auto Flash Module
Generator Voltage Build Up Latching Relay
Specifications
Input Voltage
DC 10-30 Vdc
Sensing Voltage
AC 120 / 240 Vac
Flash Time
1-8 sec. (Adjustable)
Trigger Contact
Oil pressure or fuel sensor
Resistance
0, 5, 10, 15 ohms select by jumper
Protection
Reverse current protection
Dimensions
107.0 (L) x 75.0 (W) x 44.0 (H) mm
Weight
210 g +/- 2%
*All manufacturer names, numbers, symbols and descriptions are used for reference purpose only and do not imply that any part is the product of
these manufacturer.
Mechanical Specifications & Wiring Diagram
44.0
75.0
59.0
15.5
Flash timer adj.
A
Oil pressure or fuel switch. (normally open)
B
C
1~8 Sec
_
+
B+
107.0
91.0
EB500
Battery
BFF+
5 Ohm
B
C
AC1
AC2
10 Ohm
F-
5.0
NOTE :
ALL OPEN FOR 15 Ohm
JUMP A-B FOR 10 Ohm
JUMP B-C FOR 5 Ohm
JUMP A-C FOR 0 Ohm
F+
AC1
AC2
AUTOMATIC VOLTAGE
REGULATOR (A.V.R)
Field
A
G
~
TEL : +886-7-8121771
FAX : +886-7-8121775
Headquarters : No.3, Lane 201, Chien Fu St., Chyan Jenn Dist., Kaohsiung 80664, TAIWAN
Please link to http://www.kutai.com.tw for detailed manual.