AMF-100 pages
AMF-10
Automatic Mains Failure Control & Protection Module
Features
Micro-processor auto control & protection
Easy to read high light LED display
Modularity design, easy to install
Compact size with vibration protected
Waterproof front panel with IP65
Provide full mains and genset alarms signals shutdowns
All functions setting can be done directly on AMF-10 no need for PC
connection*1
Universal LED graphic interface, displays ATS and genset status and
failures
Optional USB / RS485 / Ethernet remote communication functions
Free APP for monitor and operate your ATS & genset directly from your
smart phone
Protection & Alarm Status Indicators
Engine Start Failure
Emergency Stop
High Coolant Temperature
Low Oil Pressure
Engine Over Speed
Generator Over Load
Low Fuel Level
Abnormal Battery Voltage
Maintain Service Alarm
Customized settings are auto-saved into memory and will remain even when
power is off.
4 Digit 7 Segment Easy-to-Read LED Display
Engine Under Speed
Abnormal AC Voltage
*1
Programmable Alarm
Programmable Display with 3 Phase Volts, Amp & Freq.
Engine Operation Hours & Battery Voltage Display
Internal Program Settings & Status
Failure Signal Status By Graphic Display
Specifications
Power Input
Voltage 9~36 VDC (12V , 24V)
CT Specification
Burden
Sensing Input
Voltage 15~510 VAC
CT Secondary Rated Amps
5A
Frequency 50/60 Hz
Power Dissipating
Max. 5 watt
DC
10 Amps @ 12/24 VDC
AC
Rated Output Capacity
Above 2.5 VA
8 Amps @ 250 VAC
Operation Temperature
-20~70℃
Relative Humidity
Maximum 95%
Mechanical Specifications
(Unit : mm)
Max. Vibration
5~25 Hz , ±1.6 mm
25~100Hz , a=4g
Physical Specification
Panel Cut-Out
137.0 x 137.0 ±0.5 mm
Dimensions
147.8 (L) x 147.8 (W) x 62.3 (H) mm
Weight
589 g ±2%
TEL : +886-7-8121771
FAX : +886-7-8121775
Office: No.3, Lane 201, Chien Fu St., Chyan Jenn Dist., Kaohsiung 80664, TAIWAN
Please link to http://www.kutai.com.tw for detailed manual.