GCU-300 pages
GCU-30
Manual Key Start Genset Control Unit
Features
Microprocessor Based Design
Universal LED Graphic Interface, Displays Generator Status and
Failures
Modular Design, Quick Installation
Waterproof Front Panel With UV Protection
Charge Alternator Failure Protection
Two Push Button for Start and Pre-Heat
Three DIP Switches For Specification Setting
Suitable for Most Available Genset on The Rental Market
Specifications
DC Supply
9.0 to 36 VDC
Start Signal Output
1.2 Amp @ 12/24 VDC
Rated AC Input Voltage
5~500 VAC
Preheat Signal Output
1.2 Amp @ 12/24 VDC
AC Frequency
50/60 Hz
Charge Motor Excitation Signal Output
Fuel Solenoid Signal Output
1.2 Amp @ 12/24 VDC
Power Consumption
Environment
12/24 VDC
Under 3 watt
Physical Specification
Operating Temperature
-20~70 ℃
Panel Cut-Out
66.0 x 66.0 ±0.5 mm
Storage Temperature
-40~85 ℃
Dimensions
72.0 (L) x 72.0 (W) x 37.0 (H) mm
Relative Humidity
Maximum 90%
Weight
101 g ±2%
System Setting
Protection & Alarm Status Indicators
SW1
AC Frequency
ON50 Hz
OFF60 Hz
High Water Temperature Protection
SW2
Engine Stop Mode
ONEnergized to Start
OFFEnergized to Stop
Low Oil Pressure Protection
SW3
Engine Stop Timer Delay
ON20 sec.
OFF10 sec.
Engine Over speed Protection
Charge Alternator Failure Protection
User Define Protection
Mechanical Specifications
(Unit : mm )
TEL: +886-7-8121771
FAX: +886-7-8121775
Head Office: No.3, Lane 201, Chien Fu St., Chyan Jenn Dist., Kaohsiung, TAIWAN