KCU-04
CAN Bus J1939 Decoder Module
Specifications
Power Input
5 Vdc
Power Consumption
< 1.0 watt
Operation Temperature
-20 - +70 °C
Relative Humidity
Max. 95%
CAN Bus Communication Protocol
SAE-J1939
Dimensions
35.0 (L) x 23.0 (W) x 65.0 (H) mm
Weight
27.6 g +/- 2%
Features
Supports and decodes CAN Bus SAE-J1939 protocol to provide controller with necessary sensing information
Replace Coolant Temperature, Oil Pressure, Engine Speed(MPU) Sensor
Provide Warning Message
Equipped with LED status indicator
J1939 Decode Item :
Engine coolant temperature
Range : -40 - +210 °C , Once Per Second
Engine oil pressure
Range : 0-1000 kPa , Once Per 0.5 Second
Engine speed
Range : 0-8031 RPM , Once Per 0.5 Second
Warning Message
Over Speed, Low Speed, Low oil pressure, High coolant temperature, Low fuel level, Low Battery Voltage and
Other, Warning Message, Once Per Second
CAN Bus Network Diagram
Mechanical Specifications
23.0
35.0
4.0
65.0
STATUS
Shield
CAN-L
CAN-H
J1939
KCU-04
TEL : +886-7-8121771
FAX : +886-7-8121775
Headquarters : No.3, Lane 201, Chien Fu St., Chyan Jenn Dist., Kaohsiung 80664, TAIWAN