SL20.3010 pages
All-rounder
SL20.300
SL20.301
EMC and
Low Volt.
Directive
Data sheet
UL60950 E137006
CUL/CSA-C22.2
No. 60950
•
•
•
•
•
Input: 3 AC 400V / 3 AC 480V
Output: 24...28V / 480W (600W)
92% efficiency
Ideal for parallel operation
Simple fusing
CB
scheme
IEC60950
Input
Input voltage
UL508 LISTED
IND. CONT. EQ.
18 WM, 60°C
Output
SL20.300: 3 AC 400 V, – 15 %, + 20 %
SL20.301: 3 AC 480 V, – 15 %, + 20 %
(SL20.100: AC 230 V, s. separate data sheet)
47-63 Hz, Suitable for IT power systems
Output voltage
Rated Tolerances
• Continuous
operation
• Short term (1 min)
at 24 V/20 A
SL20.300: 340-479 V ACresp. 450-700 V DC
SL20.301: 408-576 V AC resp. 550-820 V DC
SL20.300: 300-550 V AC resp. 370-790 V DC
SL20.301: 360-620 V AC resp. 450-890 V DC
Ambient temperature
range Tamb
Input current
3 x 1.5 A
Inrush current
< 15 A at 440 V AC, < 17 A at 480 V AC
Output noise suppression Radiated EMI values below EN50081-1, even
Silent Switcher ™
when using long, unscreened output cables.
Operation: 0°C...+70°C (>60°C: Derating)
Storage: -25°C...+85°C
Rated continuous loading with convection cooling
< 2 A2s
To be fused with a 3 x 10A, B-type 'circuit-breaker' switch based on the
usual thermomagnetic overload sensing principle (used anyway to fuse
the input lines; unit has no internal fuses).
Harmonic current
emissions (PFC)
Active transient filter incorporated, so transient resistance acc.to VDE 0160 / W2 (1300 V /
1.3 ms), for all load conditions.
Hold up time
> 11 ms
at 24 V/20 A, Vinnom
24 V / 20 A (480 W) resp. 28 V / 18 A (504 W)
24 V / 25 A (600 W) resp. 28 V / 22 A (616 W)
short-term also at 60 °C
Derating
typ. 12 W/K
Voltage regulation
better than 2% over all
< 20 mVPP (i.e. < 0.1 %) incl. spikes
20 MHz bandwidth, 50 Ω measurement
(at Tamb=+60°C...+70°C)
Over-voltage protection At 32 V ± 10%: switch to hiccup mode
Front panel indicators:
• Green LED on, when Vout > UT, where UT is
ca. 2 V below Vout adjusted (24V...28V)
• Red LED on, when 14 V < Vout< UT
• Red LED flashes, when 0 V < Vout < 14 V
Parallel operation
Yes, up to ten SL20 units
acc. EN 61000-3-2
Transient
handling
• Tamb=0°C - 60°C
• Tamb=0°C - 45°C
Ripple
Inrush current limiting done with a fixed 47R resistor (not a thermistor)
which is bridged after the unit is running, so losses are minimised. That
means no reset time even at a warm-start.
Fuse loading
24...28 V DC, adjustable by (covered) front
panel potentiometer; preset: 24 V ±0.5%
Adjusting range guaranteed
To achieve current sharing the output V/I characteristic can be altered to
be 'softer' (25V at 0.4A, 24V at 20A). This is done by repositioning a
bridge connection (without opening the unit).
Reverse power immunity > 30 V
Efficiency, Reliability etc.*
Efficiency
typ. 92 %
(24 V/20 A, Vinnom)
Losses
typ. 42 W
(24 V/20 A, Vinnom)
MTBF
310.000 h acc. to Siemensnorm SN 29500
(24 V/20 A, Vinnom, Tamb = +40 °C)
Life cycle (electrolytics)
The unit exclusively uses longlife electrolytics,
specified for +105°C (cf. ’The SilverLine’, p.2).
High reliability, as
• only four aluminium electrolytics and
• no small aluminium electrolytics are used.
*
For further information see data sheets „The SilverLine“, „SilverLine Family
Branches“ and mechanics data sheet
Order information
Order number
Description
SL20.300
SL20.301
SLZ02
400 V input
480 V input
Screw mounting set, two needed per unit
sl20e300 / 031001
1/2
"