SL20.1010 pages
Single-Phase Power
CB
scheme
SL20.100
IEC60950
Data sheet
UL508 LISTED
IND. CONT. EQ.
18 WM, 60°C
•
•
•
•
•
Input: AC 230V
Output: 24-28V / 480W (600W)
91% efficiency
Ideal for parallel operation
Simple fusing
Input
Input voltage
EMC and
Low Volt.
Directive
Output
AC 230V, +15%, – 20%
47...63Hz
(SL20.300/.301: 3 AC 400/480V,
see separate data sheet)
Rated Tolerances
• Continuous
operation
• Short term (1 min)
at 24 V/20 A
AC 184...264V resp.
DC 270...370V
AC 170...280V resp.
DC 250...400V
Input current
5A
Inrush current
typ. 33A at AC 264V
Inrush current limiting done with a fixed 15R resistor (not a thermistor)
which is bridged after the unit is running, so losses are minimised. That
means no reset time even at a warm-start.
Fuse loading
UL60950 E137006
CUL/CSA-C22.2
No 60950
<10A2s
Unit is internally fused (fuse not accessible). For external fusing of unit
and for input line protection, use circuit breaker with B-characteristic
10A or slower action, or alternatively T10A HBC fuse.
Output voltage
DC 24-28V adjustable by (covered) front panel
potentiometer, preset: 24.0V ±0.5%
Adjustment range guaranteed
Output noise
suppression
Radiated EMI values below EN61000-6-3, even
when using long, unscreened output cables.
Ambient temperature
range Tamb
Operation: 0°C...+70°C (>60°C: Derating)
Storage: -25°C...+85°C
Rated continuous loading with convection cooling
• Tamb=0°C - 60°C
• Tamb=0°C - 45°C
24V/20A (480W) resp. 28V/18A (504W)
24V/25A (600W) resp. 28V/22A (616W)
short-term also at 60°C
Derating
typ. 12W/K
Voltage regulation
better than 2% over all
Ripple
• Output charact. S
• Output charact. P
(incl. spikes (20MHz bandw.), 50Ω measurem.)
<20mVPP (<0.1%)
<40mVPP (In: AC 230V, Out: 24V/20A)
<100mVPP (In: AC 184V, Out: 24V/20A)
(S/P: Single/Parallel Mode)
(at Tamb= +60°C...+70°C)
Harmonic current
emissions (PFC)
SL20.100 on request
SL20.101 acc. to EN61000-3-2
Over-voltage
protection
Transient
handling
Active transient filter incorporated, so transient resistance acc.to VDE 0160 / W2 (750V/
1.3ms), for all load conditions.
Hold up time
>20ms
at AC 230V, 24V/20A
Front panel indicators: • Green LED on, when Vout > UT, where UT
is ca. 2 V below Vout adjusted (24V...28V)
• Red LED on, when 14V < Vout< UT
• Red LED flashes, when 0V < Vout < 14V
Parallel operation
At 33V ±10%: switch to hiccup mode
Yes, up to ten SL20 units
To achieve current sharing the output V/I characteristic can be altered
to be 'softer' (25V at 0.4A, 24V at 20A). This is done by repositioning a
bridge connection (without opening the unit).
Efficiency, Reliability etc.*
Efficiency
typ. 91%
(AC 230V, 24V/20A)
Losses
typ. 48W
(AC 230V, 24V/20A)
MTBF
310.000h acc. to Siemensnorm SN 29500
(24V/20A, AC 230V, Tamb = +40°C)
Life cycle (electrolytics)
The unit exclusively uses longlife electrolytics,
specified for +105°C (cf. ’The SilverLine’, p.2).
High reliability, as
• only four aluminium electrolytics and
• no small aluminium electrolytics are used.
* For further information see data sheets „The SilverLine“,
„SilverLine Family Branches“ and mechanics data sheet
Power Back Immunity
>30V
Construction / Mechanics *
Housing dimensions and Weight
• WxHxD
• Free space for
ventilation
• Weight
220mm x 124mm x 102mm (+ DIN rail)
above/below 70mm recommended
left/right 25mm recommended
SL20.100: 1800g
SL20.101: 2400g
Design advantages:
• All connection blocks are easy to reach as mounted at the front
panel.
• PVC insulated cable can be used for all connections, as the connection blocks are mounted in the cooler area on the underside of the
unit.
Order information
Order number
SL20.100 (Basic version*),
SLS20.100 (Safety Cover*),
SLZ01
sl20e100 / 050923
Description
including PFC: SL20.101
including PFC: SLS20.101
Screw mounting set,two needed per unit
1/2