48-56V adjustable, PFC
CB
scheme
SL10.106
IEC60950
Data sheet SilverLine
UL508 LISTED
IND. CONT. EQ.
18 WM, 60°C
• Input: AC 230/115V, DC 240...375V
• Output: 48-56V/240W
• PULS Overload Design™:
Power boost up to 288W;
high overload current,
no switch-off
• Robust mechanics and EMC
Input
Input voltage
UL60950 E137006
CUL/CSA-C22.2
No 60950
EMC and
Low Volt.
Directive
Output
AC100-120/220-240V (switchable), 47-63 Hz
(AC 85...132/176...264V, DC 240...375V)
Output voltage
DC 48-56V, adjustable by (covered) front panel potentiometer; preset: 48 V ±0.5%
Adj. range guaranteed
Ambient temperature
range Tamb
Operation: 0°C...+70°C (>60°C: Derating)
Storage: -25°C...+85°C
Note: At DC input, always leave the switch in the 230V position
Input current In
<6A (switch in 115V position)
<2.8A (switch in 230V position)
Inrush current Ipk
<37A at AC 264V (Tamb = +25°C, cold start)
<62A at AC 264V (Tamb = +50°C, cold start)
Fuse loading I²t
<2.5A²s (Tamb = +25°C, cold start)
<6A²s (Tamb = +50°C, cold start)
DCin at open output
8mA (preserves battery sources)
Unit is internally fused (fuse not accessible). For external fusing of unit
and for input line protection, use circuit breaker with B-characteristic
10A or slower action, or alternatively T10A HBC fuse.
Rated continuous loading with convection cooling
• Tamb=0°C - 60°C
• Tamb=0°C - 45°C
48V/5A (240W) resp. 56V/4.3A (240W)
48V/6A (288W) resp. 56V/5.1A (288W)
short-term also at 60°C
Output is protected against short-circuit, open circuit and overload
Derating
typ. 6W/K
(at Tamb = +60°C...+70°C)
Voltage regulation
better than 2% Vout overall
Ripple / Noise
<50mVPP, (20MHz bandw., 50Ω measurement)
Parallel operation
possible; however, no equal load sharing
Harmonic current
emissions (PFC)
according to EN 61000-3-2
Power factor: better than 0.68 at nominal
load
Transient
handling
Transient resistance acc. to VDE 0160 / W2
(750V/1.3ms), for all load conditions.
Overvolt. protection
typ. 59V
Power back immunity
60V
Hold up time
>25ms at AC 196V, 48V/5A
(see Diagram overleaf)
Front panel indicator
Green LED on front panel
Construction / Mechanics*
Efficiency, Reliability etc.*
Efficiency
>90%
(AC 230V, 48V/5A)
Losses
<26.7W (AC 230V, 48V/5A)
MTBF
425.000h acc. to Siemensnorm SN 29500
(48V/5A, AC 230V, Tamb = +40°C)
Life cycle (electrolytics)
The unit uses longlife electrolytics, specified
for +105°C (cf. ’The SilverLine’, p.2).
Housing dimensions and Weight
• WxHxD
• Free space for
ventilation
• Weight
120mm x 124mm x 102mm (+ DIN rail)
above/below 25mm recommended
left/right 15mm recommended
980g
Design advantages:
• All connection blocks are easy to reach as mounted at the front
panel.
* For further information see data sheets „The SilverLine“,
„SilverLine Family Branches“ and mechanics data sheet
Ordering information
Order number
SL10.106
SLZ14
SLZ02
sl10e106 / 040511
Description
SilverLine switched-mode power supply
Adapter for S7-300 rail
Wall mounting set