YRM2.DIODE0 pages
YRM2.DIODE
DC24-48V, 20A, DUAL REDUNDANCY MODULE
Y-Series
REDUNDANCY MODULE
Cost Effective Solution to Build Redundant Systems
Dual Input with Single Output
Alarm Relay-contacts for Each Input Path
Two Diodes (Common Cathode)
DC 24-48V ±25% (18-60Vdc) Wide-range Input
Full Power Between -40°C and +60°C
Width only 32mm
Rugged Metal Housing
Large Screw Terminals
Easy Wiring:
Distribution Terminal for Negative Pole Included
3 Year Warranty
GENERAL DESCRIPTION
SHORT-FORM DATA
The YRM2.DIODE is a redundancy module, which can be
used to build 1+1 and N+1 redundant systems. It is
equipped with two input channels, which can be
connected to power supplies with up to 10A output
current and one output, which can carry nominal
currents up to 20A. The module is suitable for power
supplies with constant current overload behavior as well
as any kind of “Hiccup” overload behavior.
Input voltage
Input voltage
range
Input current
The YRM2.DIODE has a monitoring circuit included and
is the perfect solution when the power supply has no
DC-OK function. Two LEDs and two relay contacts signal
when one of the two DC-input voltages is not in range
due to a non-functioning or disconnected power supply.
In addition to the YRM2.DIODE is the YR2.DIODE which
has no monitoring circuitry included. This is the perfect
fit when the power supply itself is already equipped
with a DC-OK signal (e.g.: DIMENSION Q-Series).
Large screw terminals allow an easy installation and a
huge international approval package for a variety of
applications makes this unit suitable for nearly every
situation.
ORDER NUMBERS
DC 24-48V
18-60Vdc
Output current
±25%
2x 0-10A
2x 0-16A
0-20A
20-32A
25A
continuous
for 5 seconds
continuous
for 5 seconds
at cont. overload/
short circuit
input: 2x5A
input: 1x10A
input: 2x10A
at no load
input: 2x5A
input: 1x10A
input: 2x10A
operational,
+60 to +70°C
WxHxD
Input to output
voltage drop
typ. 0.78V
typ. 0.85V
typ. 0.85V
Power losses
typ. 1.0W
typ. 8.8W
typ. 9.5W
typ. 18W
Temperature range -40°C to +70°C
Derating
0.5A/°C
Dimensions
32x124x117mm
MARKINGS
Redundancy
Module
YRM2.Diode
24-48V Standard unit
Accessory
ZM1.WALL
Wall/ panel mount
bracket
Side mount bracket
IND. CONT. EQ.
ZM11.SIDE
UL 508
IECEx
UL 60950-1
ATEX
II 3G Ex nA nC IIC T4 Gc
Marine
Apr. 2014 / Rev. 1.4 DS-YRM2.DIODE-EN
All parameters are specified at 24V, 20A output current, 25°C ambient and after a 5 minutes run-in time unless otherwise noted
www.pulspower.com Phone +49 89 9278 0
Germany
Class I Div 2
EMC, LVD
1/19
"